Combustible gas detector EVIKON E2630-LEL, warning signal: visual + acoustic, power supply: 90...265 VAC, typical detection range range: 0-100% LEL. More information

  • Availability

    GLS delivery 3-4 working days. DHL express delivery 1-2 working days.

  • More than 5 pcs in stock  
     
Price without VAT € 158,49
Price with VAT 21 % € 191,77

Varianty produktu

+

Would you like to get a price offer? Contact us

Parameters and catalogs

Detector type Stationary
Output signal Switching relay
Power 230 VAC
Type of gas LPG-Propane-Butane, CH4-Methane, H2-Hydrogen, C4H10-Butane, C3H8-Propane, C2H2-Acetylene
Weight 0.35 kg

Datasheet download

Download PDF

Declaration of Conformity download

Download PDF

INSTALLATION INSTRUCTIONS download

Download PDF

Evikon E2630-LEL combustible gas detector

The gas detector is used to detect and warn early of a dangerous (explosive or toxic) concentration of the sensed gas. The sensor is suitable for underground parkings, boiler houses, kitchens, and other confined spaces, where potentially explosive concentration of combustible gases can accumulate. The detector is equipped with two-level signaling - visual (LED) and acoustic (85db). Two relays with switch-over contact may be used for remote signalling or ventilation control. Possibility of connection via UART interface.

Made in robust design with IP65 protection - ABS plastic, resistant to mechanical damage. Rigid, tough, resistant to low and high temperatures, poorly absorbent, harmless to health.

The service life of the sensor is more than 10 years.

The default alarm set-points are at 10% and 20% of the lower explosion limit (LEL). The recommended coverage area per detector is 80-120 m2, 5-6m radius.

Each detector is factory calibrated (10 and 20% LEL). The law states that recalibration must be performed at least once every 12 months. Calibration may only be performed by a person certified by the manufacturer.

Do not hesitate to contact us for recalibration!

The detector is designed to detect flammable gases:
Methane (CH4), Propane (C3H8), Butane (C4H10), Hydrogen (H), Acetylene (C2H2)

DETECTOR CALIBRATED FOR METHANE.

Features:

  • Selective, sensitive and stable detection of flammable gases
  • Long-life metal-oxide sensor
  • Wall-mount IP65 protected housing
  • Acoustic and visual alarm 
  • Two output relays for alarm/ventilation control

Tip: Get notified by the service about the date of legal calibration www.kalibrovat.cz