Questions? +32 460 226 991 (English). EU-wide delivery!

Differential pressure controller IMI TA DA 516 DN 40/50 G 2" with measuring points

Differential pressure controller IMI TA DA 516 DN 40/50 G 2" with measuring points

IMI Hydronic Engineering
  • Product code: 52795040
  • EAN : 3831112507197
  • Manufacturer code: 52795040
  • Warranty: 2 years

Differential pressure regulator IMI TA series DA 516 DN 40/50 in connection size G 2 "with measuring nipples. More information

  • Availability

    GLS delivery 3-4 working days. DHL express delivery 1-2 working days.

  • In stock 1 pcs  
     
List price € 1 441,22
Price without VAT € 976,69
Price with VAT 21 % € 1 181,79
+

Would you like to get a price offer? Contact us

Parameters and catalogs

Connection size 2"
Dimension (DN) DN 50, DN 40
Pressure PN 16
Pressure range 5...30 kPa
Weight 5.80 kg

CATALOG SHEET download

Download PDF

INSTRUCTIONS download

Download PDF

The regulator is continuously adjustable for pressure differences of 5-30 kPa. It is suitable for heating or cooling applications demanding high temperatures or high pressure differences. The installation is performed on the return pipe on both the primary and secondary side of the systems in the flow direction shown on the regulator body. The operation of the controller is very quiet. Thanks to the measuring nipples, precise balancing processes are achieved.

Construction and function

1. Diaphragm - the pressure from the supply line acts on the diaphragm through the impulse line Δp + and thus closes the regulator

2. Venting screws - after filling the system, it is advisable to vent the controller body

3. Spring - acts on the diaphragm on the other side and, together with the pressure conducted by the integrated channel from the return pipe, causes the valve to open

4. Locking screw - secures the setting values on the ring

5. Adjusting ring - affects the force of the spring. If the spring force and the pressures acting on the diaphragm are balanced, a constant pressure difference is achieved.

Properties

  • connection size G 5 "
  • differential pressure range 5-30 kPa
  • max pressure 16 bar
  • max temperature 120 ° C
  • EPDM seal
  • external thread
  • measuring nipples
  • flow 30 m3 / h

Use

We respond to your product queries as quickly as possible, usually within 24 hours.

Didn't find what you wanted to know?