The Honeywell RV280-11/4A non-return valve with a 1 1/4" threaded connection prevents backflow of drinking water in accordance with EN 1717. Spring-operated, suitable for installation in any position. Max. pressure 16 bar, kvs 28 m³/h. More information
Delivery to Belgium (days are avarages)
DHL Express: 8.2 workdays, € 16,94
| Connection size | 1 1/4" |
| Connection Type | Threaded |
| Nominal diameter | DN 125 |
| Pressure | PN 16 |
| Temperature | 65 °C |
| Weight | 0.80 kg |
Catalog sheet eng download
Download PDFHoneywell (Resideo) RV280-11/4A is a check valve with a 1 1/4" female thread, designed as a standalone protection device against backflow of water. It prevents reverse flow, back pressure and back siphonage in accordance with the requirements of EN 1717.
The valve is used in potable water systems in both commercial and industrial installations, typically immediately downstream of the water meter. It is also suitable for central heating systems, as a safety element for liquids, downstream of pumping equipment or upstream of water heating equipment. In addition to water, the valve can also be used with petroleum, compressed air, paraffin, petrol or heating oil; however, it is not suitable for steam, heavy oils or benzole.


The spring-loaded disc closes against the seat and lifts off it in proportion to the flow rate. As soon as the flow rate drops towards zero, the spring returns the disc to the seat and seals the waterway – the force exerted by the spring is always lower than the pressure of the flowing medium, so the valve remains open to flow. The opening pressure is approximately 0.05 bar, so the valve does not create pressure surges and has a low pressure loss. The valve can be installed in any position.
Technical parameters (1 1/4" version):
The valve can be installed in any position. For horizontal installation, the manufacturer recommends turning the drain plug downwards, which makes draining easier if required.
The valve is intended for potable water, but it can also be used with petroleum, compressed air, paraffin, petrol or heating oil. It is not suitable for steam, heavy oils or benzole.
Yes, according to EN 1717, regular inspection of check valves is recommended to ensure their correct operation.
Yes, the manufacturer recommends fitting shut-off valves upstream and downstream of the valve to ensure easy servicing and better accessibility during maintenance.
We respond to your product queries as quickly as possible, usually within 24 hours.