Differential pressure controller with capillary T&A STAP for heating and cooling system circuits with control valves. DN 15, with drainage option. More information

  • Delivery

    Delivery to Belgium (days are avarages)

    FedEx:
    2.6 workdays € 7,02
    Bpost HD (Home Delivery):
    3.2 workdays € 10,64
    BPost - PP (Pick-up Point):
    3.5 workdays € 9,91
    FedEx Priority:
    1.7 workdays € 12,71
    DHL Express:
    1.6 workdays € 16,94

    DHL Express: 1.6 workdays, € 16,94

  • In stock 1 pcs  
     
List price € 342,55
Price without VAT € 155,70
Price with VAT 21 % € 188,40
+

Parameters and catalogs

Capillary length 1 m
Connection size 1/2"
Dimension (DN) DN 15
Pressure PN 16
Pressure range 5...25 kPa
Weight 1.10 kg

Catalog sheet download

Download PDF

Assembly instructions download

Download PDF

Differential pressure controller for closed heating or cooling system circuits. It helps protect control valves from pressure fluctuations and balances the systems to maintain a constant pressure difference. The controllers are characterized by high precision and compact dimensions, allowing for a wide range of connection possibilities.

The precision of the controller is ensured by a balanced cone inside the controller and a measuring nipple, which features a drainage option, facilitating the balancing processes. The controller allows for the setting of an exact desired balancing value. It also includes a shut-off function for easy installation and operation.

Construction

  1. ΔpL setting (with a hex key)
  2. shut-off
  3. capillary connection - venting - connection for STAP measuring nipple
  4. measuring nipple
  5. connection for drainage adapter (accessory)

Features

  • pressure PN 16
  • capillary length 1 m
  • max pressure difference 250 kPa
  • factory setting range 5-25 kPa
  • connection size G 1/2" internal thread
  • nominal diameter DN 15
  • operating temperature range -20...120 °C
  • flow rate 1 m3/h
  • compatible with KOMBI compression fittings

We respond to your product queries as quickly as possible, usually within 24 hours.

Didn't find what you wanted to know?