Mechanical disconnector protecting drinking water distribution from contamination to risk class 4 in accordance with EN1717. More information
Out of stock - can be requested
Would you like to get a price offer? Contact us
Max. flow | 14 m3/h |
Max. operating pressure | 16 bar |
Max. water temperature | 40 °C |
Medium | Drinking water |
Weight | 9.70 kg |
Datasheet download
Download PDFThe mechanical disconnector protects drinking water systems from contamination due to back flow and back syphonage of non-potable water into the public water supply network. Conforms to DIN1988 part 4 of type 1 design. It offers better protection than check valves as it allows protection up to risk class 4.
Compact, easy-to-maintain design, eliminating the need to remove the separator from the pipeline. The disconnector is characterized by low pressure loss and high flow rate. When the disconnector is closed, a green color appears under the transparent cover. The disconnector is certified for use in drinking water installations and is KTW approved.
Available in four versions with different opening pressure - A 0,5 bar, B 1 bar, C 1,5 bar, D 2 bar
The inlet pressure operates on the annular surface of the valve piston and pushes it against the force of the spring bringing the piston to the open position. If the supply pressure falls below the opening pressure needed to overcome the spring force then the integral spring pushes the valve into the closed position.